Standard series · ILR

ILR line / commutation reactors, uk 2 % and 4 %, 400 V

84 standard three-phase line reactors for frequency converters, rectifiers and drives – 2 A to 400 A, uk 2 % and 4 % at 400 V 50 Hz, in insulation class F and class B. Aluminium winding as standard (copper on the smallest ratings), the other conductor as an option.

Preliminary · design data

Input reactors reduce the current harmonics and the rms input current of 6-pulse converters, limit commutation notches and protect the DC link and rectifier from network transients. Linear up to 1.6 × In; losses rated with converter harmonics.

2 – 400 ARated current In, 21 steps
uk 2 · 4 %At 400 V 50 Hz
≥ 95 %of Ln at 1.6 × In
Al standard · Cu optionWinding; copper standard on the 2–10 A types
Class F / BIEC 61558-1, with 2.5 K design margin
45 °CMax. ambient, natural convection

Terms and how to choose

uk (%)Voltage drop across the reactor at rated current, as a percentage of the phase voltage. It defines the inductance: L = uk × Uph / (2π × 50 Hz × In).
uk = 2 %Low voltage drop. Limits current peaks and commutation notches and protects the rectifier; moderate reduction of harmonic currents.
uk = 4 %The usual choice for 6-pulse drives: a clearly lower harmonic current and rms input current, with about twice the voltage drop of 2 %.
In (A)Rated continuous current of the drive or converter, including its harmonics. Choose the reactor with In ≥ the input current of the drive.
n1 × n2 (mm)Mounting hole pitch of the feet (width × depth).

Part number: LR3063-50-471-AL = LR3 three-phase line reactor · 063 = rated current 63 A · 50 = 50 Hz · 471 = inductance code in µH (47 × 10¹ µH = 0.47 mH, uk 4 % at 400 V) · -AL = aluminium winding (no suffix = copper) · -C01 = insulation class B version (no suffix = class F). Hover a part number to see the former type designation.

Product table – 84 types: pick class, uk and current

Every type is available with aluminium or copper winding – same ratings and inductance; losses, weight and dimensions differ. Choose the winding to see its data; standard marks the standard version.

WindingClassukCurrent

Part no.In
A
L
mH
Losses
W
Weight
kg
A × B × C
mm
n1 × n2
mm
Data­sheet
LR3002-50-742-AL27.351131.3106 × 80 × 15275 × 50PDF
LR3002-50-742standard27.351121.4106 × 80 × 15275 × 50PDF
LR3004-50-372-AL43.676171.4108 × 80 × 15280 × 50PDF
LR3004-50-372standard43.676151.5107 × 80 × 15275 × 50PDF
LR3006-50-252-AL62.45221.4113 × 85 × 15285 × 55PDF
LR3006-50-252standard62.45171.7109 × 85 × 15280 × 55PDF
LR3008-50-182-AL81.838262.1110 × 95 × 15280 × 65PDF
LR3008-50-182standard81.838222.4110 × 95 × 15280 × 65PDF
LR3010-50-152-AL101.47292.1112 × 95 × 15280 × 65PDF
LR3010-50-152standard101.47252.5112 × 95 × 15280 × 65PDF
LR3013-50-112-ALstandard131.131352.2114 × 100 × 15285 × 70PDF
LR3013-50-112131.131282.6113 × 95 × 15285 × 65PDF
LR3016-50-921-ALstandard160.919432.8140 × 95 × 177110 × 65PDF
LR3016-50-921160.919353.4139 × 95 × 177110 × 65PDF
LR3020-50-741-ALstandard200.735522.9143 × 95 × 177115 × 65PDF
LR3020-50-741200.735413.6142 × 95 × 177110 × 65PDF
LR3025-50-591-ALstandard250.588604.1140 × 105 × 177110 × 75PDF
LR3025-50-591250.588473.9144 × 100 × 177115 × 70PDF
LR3032-50-461-ALstandard320.459724.8165 × 100 × 202135 × 70PDF
LR3032-50-461320.459555.2144 × 110 × 177115 × 80PDF
LR3040-50-371-ALstandard400.368854.9170 × 105 × 202140 × 75PDF
LR3040-50-371400.368666.1169 × 105 × 202140 × 75PDF
LR3050-50-291-ALstandard500.2941027165 × 115 × 202135 × 85PDF
LR3050-50-291500.294806.6173 × 105 × 202145 × 75PDF
LR3063-50-231-ALstandard630.2331237.1169 × 120 × 202140 × 90PDF
LR3063-50-231630.233938.7170 × 120 × 202140 × 90PDF
LR3080-50-181-ALstandard800.18415311215 × 110 × 275185 × 80PDF
LR3080-50-181800.18411211.2170 × 135 × 217140 × 105PDF
LR3100-50-151-ALstandard1000.14718111.2220 × 115 × 275190 × 85PDF
LR3100-50-1511000.14714413.4220 × 115 × 275190 × 85PDF
LR3125-50-121-ALstandard1250.11818212224 × 120 × 275195 × 90PDF
LR3125-50-1211250.11815714.7219 × 115 × 275190 × 85PDF
LR3160-50-920-ALstandard1600.09221017.4230 × 145 × 275200 × 115PDF
LR3160-50-9201600.09218416.1224 × 120 × 275195 × 90PDF
LR3200-50-740-ALstandard2000.07428222274 × 130 × 340245 × 100PDF
LR3200-50-7402000.07420822.5230 × 145 × 290200 × 115PDF
LR3250-50-590-ALstandard2500.05931622.8280 × 135 × 340250 × 105PDF
LR3250-50-5902500.05926826.8224 × 160 × 290195 × 130PDF
LR3315-50-470-ALstandard3150.04738531.1304 × 135 × 370275 × 105PDF
LR3315-50-4703150.04731629.6280 × 135 × 340250 × 105PDF
LR3400-50-370-ALstandard4000.03745232.9328 × 160 × 370300 × 130PDF
LR3400-50-3704000.03738638.2304 × 135 × 370275 × 105PDF
LR3002-50-153-AL214.702151.4108 × 80 × 15280 × 50PDF
LR3002-50-153standard214.702121.6108 × 80 × 15280 × 50PDF
LR3004-50-742-ALstandard47.351232.1111 × 95 × 15280 × 65PDF
LR3004-50-74247.351181.8113 × 85 × 15285 × 55PDF
LR3006-50-492-AL64.901302.1113 × 95 × 15285 × 65PDF
LR3006-50-492standard64.901242.5112 × 95 × 15280 × 65PDF
LR3008-50-372-ALstandard83.676392.8140 × 95 × 177110 × 65PDF
LR3008-50-37283.676303.4139 × 95 × 177110 × 65PDF
LR3010-50-292-ALstandard102.94452.9141 × 95 × 177110 × 65PDF
LR3010-50-292102.94353.6140 × 95 × 177110 × 65PDF
LR3013-50-232-ALstandard132.262534.1139 × 105 × 177110 × 75PDF
LR3013-50-232132.262434.8138 × 105 × 177110 × 75PDF
LR3016-50-182-ALstandard161.838644.8165 × 100 × 202135 × 70PDF
LR3016-50-182161.838485.1139 × 105 × 177110 × 75PDF
LR3020-50-152-ALstandard201.47784.9168 × 100 × 202140 × 70PDF
LR3020-50-152201.47606167 × 100 × 202135 × 70PDF
LR3025-50-122-ALstandard251.176806.9144 × 135 × 177115 × 105PDF
LR3025-50-122251.176726.6173 × 105 × 202145 × 75PDF
LR3032-50-921-ALstandard320.9191057.2170 × 120 × 202140 × 90PDF
LR3032-50-921320.919808.5144 × 135 × 177115 × 105PDF
LR3040-50-741-ALstandard400.7351249.4170 × 135 × 202140 × 105PDF
LR3040-50-741400.735959.5173 × 120 × 202145 × 90PDF
LR3050-50-591-ALstandard500.58816111.2220 × 115 × 260190 × 85PDF
LR3050-50-591500.58811611.7173 × 135 × 202145 × 105PDF
LR3063-50-471-ALstandard630.46720111.5223 × 120 × 260195 × 90PDF
LR3063-50-471630.46714514.5224 × 120 × 260195 × 90PDF
LR3080-50-371-ALstandard800.36821716.6220 × 135 × 275190 × 105PDF
LR3080-50-371800.36817315.9229 × 125 × 275200 × 95PDF
LR3100-50-291-ALstandard1000.29427621.5270 × 125 × 325240 × 95PDF
LR3100-50-2911000.29420120.5224 × 140 × 275195 × 110PDF
LR3125-50-241-ALstandard1250.23527622.6274 × 130 × 325245 × 100PDF
LR3125-50-2411250.23523222.8228 × 145 × 275200 × 115PDF
LR3160-50-181-ALstandard1600.18434930.9299 × 130 × 355270 × 100PDF
LR3160-50-1811600.18426430.7278 × 135 × 325250 × 105PDF
LR3200-50-151-ALstandard2000.14741637.9324 × 140 × 390295 × 110PDF
LR3200-50-1512000.14734337.4299 × 130 × 370270 × 100PDF
LR3250-50-121-ALstandard2500.11842240.8342 × 160 × 390310 × 130PDF
LR3250-50-1212500.11839540.3304 × 135 × 370275 × 105PDF
LR3315-50-930-ALstandard3150.09359058.9374 × 150 × 440345 × 120PDF
LR3315-50-9303150.09342655.1342 × 160 × 390310 × 130PDF
LR3400-50-740-ALstandard4000.07460863.9409 × 185 × 440380 × 155PDF
LR3400-50-7404000.07458869.5374 × 150 × 440345 × 120PDF
LR3002-50-742-AL-C0127.351131.3106 × 80 × 15275 × 50PDF
LR3002-50-742-C01standard27.351121.4106 × 80 × 15275 × 50PDF
LR3004-50-372-AL-C0143.676171.4108 × 80 × 15280 × 50PDF
LR3004-50-372-C01standard43.676151.5107 × 80 × 15275 × 50PDF
LR3006-50-252-AL-C0162.45221.4113 × 85 × 15285 × 55PDF
LR3006-50-252-C01standard62.45171.7109 × 85 × 15280 × 55PDF
LR3008-50-182-AL-C0181.838262.1110 × 95 × 15280 × 65PDF
LR3008-50-182-C01standard81.838222.4110 × 95 × 15280 × 65PDF
LR3010-50-152-AL-C01101.47292.1112 × 95 × 15280 × 65PDF
LR3010-50-152-C01standard101.47252.5112 × 95 × 15280 × 65PDF
LR3013-50-112-AL-C01standard131.131352.2114 × 100 × 15285 × 70PDF
LR3013-50-112-C01131.131282.6113 × 95 × 15285 × 65PDF
LR3016-50-921-AL-C01standard160.919432.8140 × 95 × 177110 × 65PDF
LR3016-50-921-C01160.919353.4139 × 95 × 177110 × 65PDF
LR3020-50-741-AL-C01standard200.735522.9143 × 95 × 177115 × 65PDF
LR3020-50-741-C01200.735413.6142 × 95 × 177110 × 65PDF
LR3025-50-591-AL-C01standard250.588604.1140 × 105 × 177110 × 75PDF
LR3025-50-591-C01250.588473.9144 × 100 × 177115 × 70PDF
LR3032-50-461-AL-C01standard320.459724.8165 × 100 × 202135 × 70PDF
LR3032-50-461-C01320.459555.2144 × 110 × 177115 × 80PDF
LR3040-50-371-AL-C01standard400.368854.9170 × 105 × 202140 × 75PDF
LR3040-50-371-C01400.368666.1169 × 105 × 202140 × 75PDF
LR3050-50-291-AL-C01standard500.294957.1170 × 120 × 202140 × 90PDF
LR3050-50-291-C01500.294806.6173 × 105 × 202145 × 75PDF
LR3063-50-231-AL-C01standard630.2331139.4170 × 135 × 202140 × 105PDF
LR3063-50-231-C01630.233938.7170 × 120 × 202140 × 90PDF
LR3080-50-181-AL-C01standard800.18414711.1220 × 115 × 275190 × 85PDF
LR3080-50-181-C01800.18411211.2170 × 135 × 217140 × 105PDF
LR3100-50-151-AL-C01standard1000.14715511.6224 × 120 × 275195 × 90PDF
LR3100-50-151-C011000.14714413.4220 × 115 × 275190 × 85PDF
LR3125-50-121-AL-C01standard1250.11817217.4230 × 145 × 275200 × 115PDF
LR3125-50-121-C011250.11814016.1224 × 120 × 275195 × 90PDF
LR3160-50-920-AL-C01standard1600.09222922274 × 130 × 325245 × 100PDF
LR3160-50-920-C011600.09217422.5230 × 145 × 275200 × 115PDF
LR3200-50-740-AL-C01standard2000.07424922.8280 × 135 × 340250 × 105PDF
LR3200-50-740-C012000.07422626.9274 × 130 × 340245 × 100PDF
LR3250-50-590-AL-C01standard2500.05929231.7304 × 135 × 370275 × 105PDF
LR3250-50-590-C012500.05924729.6280 × 135 × 340250 × 105PDF
LR3315-50-470-AL-C01standard3150.04734440.1342 × 160 × 390310 × 130PDF
LR3315-50-470-C013150.04729140.3304 × 135 × 370275 × 105PDF
LR3400-50-370-AL-C01standard4000.03733939.7342 × 160 × 390310 × 130PDF
LR3400-50-370-C014000.03736451342 × 160 × 390310 × 130PDF
LR3002-50-153-AL-C01214.702151.4108 × 80 × 15280 × 50PDF
LR3002-50-153-C01standard214.702121.6108 × 80 × 15280 × 50PDF
LR3004-50-742-AL-C01standard47.351232.1111 × 95 × 15280 × 65PDF
LR3004-50-742-C0147.351181.8113 × 85 × 15285 × 55PDF
LR3006-50-492-AL-C0164.901302.1113 × 95 × 15285 × 65PDF
LR3006-50-492-C01standard64.901242.5112 × 95 × 15280 × 65PDF
LR3008-50-372-AL-C01standard83.676392.8140 × 95 × 177110 × 65PDF
LR3008-50-372-C0183.676303.4139 × 95 × 177110 × 65PDF
LR3010-50-292-AL-C01standard102.94452.9141 × 95 × 177110 × 65PDF
LR3010-50-292-C01102.94353.6140 × 95 × 177110 × 65PDF
LR3013-50-232-AL-C01standard132.262534.1139 × 105 × 177110 × 75PDF
LR3013-50-232-C01132.262434.8138 × 105 × 177110 × 75PDF
LR3016-50-182-AL-C01standard161.838644.8165 × 100 × 202135 × 70PDF
LR3016-50-182-C01161.838485.1139 × 105 × 177110 × 75PDF
LR3020-50-152-AL-C01standard201.47784.9168 × 100 × 202140 × 70PDF
LR3020-50-152-C01201.47606167 × 100 × 202135 × 70PDF
LR3025-50-122-AL-C01standard251.176806.9144 × 135 × 177115 × 105PDF
LR3025-50-122-C01251.176726.6173 × 105 × 202145 × 75PDF
LR3032-50-921-AL-C01standard320.919987.4173 × 120 × 202145 × 90PDF
LR3032-50-921-C01320.919808.5144 × 135 × 177115 × 105PDF
LR3040-50-741-AL-C01standard400.73513311215 × 110 × 260185 × 80PDF
LR3040-50-741-C01400.735959.5173 × 120 × 202145 × 90PDF
LR3050-50-591-AL-C01standard500.58814811.5224 × 120 × 260195 × 90PDF
LR3050-50-591-C01500.58811611.7173 × 135 × 202145 × 105PDF
LR3063-50-471-AL-C01standard630.46716016.8224 × 140 × 260195 × 110PDF
LR3063-50-471-C01630.46714514.5224 × 120 × 260195 × 90PDF
LR3080-50-371-AL-C01standard800.36822621.4270 × 125 × 325240 × 95PDF
LR3080-50-371-C01800.36817319.5220 × 135 × 275190 × 105PDF
LR3100-50-291-AL-C01standard1000.29423722.1274 × 130 × 325245 × 100PDF
LR3100-50-291-C011000.29420425.7270 × 125 × 325240 × 95PDF
LR3125-50-241-AL-C01standard1250.23526830.9299 × 130 × 355270 × 100PDF
LR3125-50-241-C011250.23521328.8274 × 130 × 325245 × 100PDF
LR3160-50-181-AL-C01standard1600.18432837.9324 × 140 × 375295 × 110PDF
LR3160-50-181-C011600.18427037.8303 × 135 × 355275 × 105PDF
LR3200-50-151-AL-C01standard2000.14733240.8342 × 160 × 390310 × 130PDF
LR3200-50-151-C012000.14732345.8324 × 140 × 390295 × 110PDF
LR3250-50-121-AL-C01standard2500.11845559.9380 × 155 × 440350 × 125PDF
LR3250-50-121-C012500.11833255.1342 × 160 × 390310 × 130PDF
LR3315-50-930-AL-C01standard3150.09348963.9409 × 185 × 440380 × 155PDF
LR3315-50-930-C013150.09345473380 × 155 × 440350 × 125PDF
LR3400-50-740-AL-C01standard4000.07462891.4448 × 185 × 490420 × 155PDF
LR3400-50-740-C014000.07445472.3380 × 155 × 440350 × 125PDF

L per phase at In, 400 V 50 Hz (L = uk · Uph / (ω · In)), tolerance ±5 %. Losses typical at In incl. 6-pulse converter harmonics. Class F: winding ≤ 140 °C, class B: ≤ 120 °C at Ta 45 °C (IEC 61558-1, resistance method). Standard EN 61558-2-20.

Derating – higher ambient temperature and altitude (general curve)

Ratings apply up to Ta 45 °C and 1000 m with natural cooling. Above that, multiply the rated current by both factors: Iperm = kT × kH × Irated. Valid for aluminium and copper windings.

AMBIENT TEMPERATUREALTITUDE75 %80 %85 %90 %95 %100 %75 %80 %85 %90 %95 %100 %455055606570Ta (°C), natural cooling, altitude ≤ 1000 m1000200030004000altitude (m), Ta ≤ 45 °Cpermissible I / I ratedFBabove 2000 m:check insulation voltageclass F and B
General derating of all ILR types – ICD&C thermal model, IEC 61558-1 class limits minus 2.5 K
Ambient Ta (°C)455055606570
Class F – factor kT1.000.970.930.900.860.83
Class B – factor kT1.000.960.910.870.820.77
Altitude (m)1000150020002500300035004000
Factor kH (F and B)1.000.990.980.970.960.950.94

For line reactors the factor applies to the rated current In including converter harmonics; inductance and uk do not change. Example: LR3063-50-471 at Ta 55 °C and 2000 m → k = 0.93 × 0.98 = 0.91; permissible continuous current 0.91 × 63 A ≈ 57 A. For a 63 A drive choose the next rating, LR3080-50-371.

Basis: winding temperature rise ΔT ∝ P0.826 with losses ∝ I² (kT); convective heat transfer ∝ √(air density) with radiation unchanged (kH). The curves assume the type is fully loaded at its rating, so most types have some extra margin. No uprating below 45 °C. Above 2000 m the insulation clearances must be checked, especially for 690 V types; forced air or derating beyond 70 °C / 4000 m on request.

Mechanical outline – ILR series (schematic)

FRONT VIEWSIDE VIEWU1U2V1V2W1W2PENAMEPLATEn1ACn2BD
Terminals U1–U2, V1–V2, W1–W2 · PE stud
  • AOverall width (mounting feet)
  • BOverall depth (mounting feet)
  • COverall height incl. terminals
  • DWinding depth
  • n1Mounting pitch, width
  • n2Mounting pitch, depth

Schematic – not to scale. A, B, C, n1 and n2 for each type are given in the product table; the dimensioned drawing of every type is on page 3 of its datasheet. Slotted holes for M8 (M10 from A ≥ 320 mm); Cu bar terminals above 160 A.

Other voltages, 60 Hz, other uk values, output (motor) reactors, IP enclosures and forced-air ratings on request. Preliminary design data – to be confirmed on first samples. Specifications subject to change without notice.

Related series

Next step

Send us your spec.

Power, voltage, frequency, mounting and target standard – we scope design and production with you.